Filtered by vendor Siemens
Subscriptions
Total
2235 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2014-2259 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTPS packets. | ||||
| CVE-2014-2257 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted ISO-TSAP packets. | ||||
| CVE-2014-2256 | 1 Siemens | 6 Simatic S7 Cpu-1211c, Simatic S7 Cpu 1200 Firmware, Simatic S7 Cpu 1212c and 3 more | 2025-04-12 | N/A |
| Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted ISO-TSAP packets, a different vulnerability than CVE-2014-2257. | ||||
| CVE-2014-2255 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTP packets. | ||||
| CVE-2014-2253 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted Profinet packets. | ||||
| CVE-2015-4174 | 1 Siemens | 1 Climatix Bacnet\/ip | 2025-04-12 | N/A |
| Cross-site scripting (XSS) vulnerability in the integrated web server on the Siemens Climatix BACnet/IP communication module with firmware before 10.34 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. | ||||
| CVE-2014-2251 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | N/A |
| The random-number generator on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 does not have sufficient entropy, which makes it easier for remote attackers to defeat cryptographic protection mechanisms and hijack sessions via unspecified vectors. | ||||
| CVE-2014-2248 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | N/A |
| Open redirect vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors. | ||||
| CVE-2014-2247 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | N/A |
| The integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject headers via unspecified vectors. | ||||
| CVE-2014-0224 | 9 Fedoraproject, Filezilla-project, Mariadb and 6 more | 23 Fedora, Filezilla Server, Mariadb and 20 more | 2025-04-12 | 7.4 High |
| OpenSSL before 0.9.8za, 1.0.0 before 1.0.0m, and 1.0.1 before 1.0.1h does not properly restrict processing of ChangeCipherSpec messages, which allows man-in-the-middle attackers to trigger use of a zero-length master key in certain OpenSSL-to-OpenSSL communications, and consequently hijack sessions or obtain sensitive information, via a crafted TLS handshake, aka the "CCS Injection" vulnerability. | ||||
| CVE-2014-5231 | 2 Apple, Siemens | 2 Iphone Os, Simatic Wincc Sm\@rtclient | 2025-04-12 | N/A |
| The Siemens SIMATIC WinCC Sm@rtClient app before 1.0.2 for iOS allows physically proximate attackers to extract the password from storage via unspecified vectors. | ||||
| CVE-2016-7114 | 1 Siemens | 2 En100 Ethernet Module, En100 Ethernet Module Firmware | 2025-04-12 | N/A |
| A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.87; SIPROTEC 7UT686 : All versions < V 4.02; SIPROTEC 7SD686 : All versions < V 4.05; SIPROTEC 7SJ66 : All versions < V 4.30. Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations. A legitimate user must be logged into the web interface for the attack to be successful. | ||||
| CVE-2016-4953 | 5 Ntp, Opensuse, Oracle and 2 more | 15 Ntp, Leap, Opensuse and 12 more | 2025-04-12 | 7.5 High |
| ntpd in NTP 4.x before 4.2.8p8 allows remote attackers to cause a denial of service (ephemeral-association demobilization) by sending a spoofed crypto-NAK packet with incorrect authentication data at a certain time. | ||||
| CVE-2016-6204 | 1 Siemens | 1 Sinema Remote Connect Server | 2025-04-12 | N/A |
| Cross-site scripting (XSS) vulnerability in the integrated web server in Siemens SINEMA Remote Connect Server before 1.2 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. | ||||
| CVE-2016-5743 | 1 Siemens | 5 Simatic Batch, Simatic Openpcs 7, Simatic Pcs 7 and 2 more | 2025-04-12 | N/A |
| Siemens SIMATIC WinCC before 7.3 Update 10 and 7.4 before Update 1, SIMATIC BATCH before 8.1 SP1 Update 9 as distributed in SIMATIC PCS 7 through 8.1 SP1, SIMATIC OpenPCS 7 before 8.1 Update 3 as distributed in SIMATIC PCS 7 through 8.1 SP1, SIMATIC OpenPCS 7 before 8.2 Update 1 as distributed in SIMATIC PCS 7 8.2, and SIMATIC WinCC Runtime Professional before 13 SP1 Update 9 allow remote attackers to execute arbitrary code via crafted packets. | ||||
| CVE-2014-2246 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | N/A |
| Cross-site scripting (XSS) vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. | ||||
| CVE-2014-8478 | 1 Siemens | 9 Scalance X-300, Scalance X-300 Series Firmware, Scalance X-300eec and 6 more | 2025-04-12 | N/A |
| The web server on Siemens SCALANCE X-300 switches with firmware before 4.0 and SCALANCE X 408 switches with firmware before 4.0 allows remote attackers to cause a denial of service (reboot) via malformed HTTP requests. | ||||
| CVE-2016-9158 | 1 Siemens | 21 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 314, Simatic S7-300 Cpu 315-2 Dp and 18 more | 2025-04-12 | N/A |
| A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions). Specially crafted packets sent to port 80/tcp could cause the affected devices to go into defect mode. A cold restart is required to recover the system. | ||||
| CVE-2016-9155 | 1 Siemens | 30 Ccid1445-dn18, Ccid1445-dn18 Firmware, Ccid1445-dn28 and 27 more | 2025-04-12 | N/A |
| The following SIEMENS branded IP Camera Models CCMW3025, CVMW3025-IR, CFMW3025 prior to version 1.41_SP18_S1; CCPW3025, CCPW5025 prior to version 0.1.73_S1; CCMD3025-DN18 prior to version v1.394_S1; CCID1445-DN18, CCID1445-DN28, CCID1145-DN36, CFIS1425, CCIS1425, CFMS2025, CCMS2025, CVMS2025-IR, CFMW1025, CCMW1025 prior to version v2635_SP1 could allow an attacker with network access to the web server to obtain administrative credentials under certain circumstances. | ||||
| CVE-2016-3155 | 1 Siemens | 1 Apogee Insight | 2025-04-12 | N/A |
| Siemens APOGEE Insight uses weak permissions for the application folder, which allows local users to obtain sensitive information or modify data via unspecified vectors. | ||||