Filtered by vendor Schneider-electric Subscriptions
Total 781 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2022-41670 1 Schneider-electric 2 Ecostruxure Operator Terminal Expert, Pro-face Blue 2025-04-30 7 High
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in the SGIUtility component that allows adversaries with local user privileges to load malicious DLL which could result in execution of malicious code. Affected Products: EcoStruxure Operator Terminal Expert(V3.3 Hotfix 1 or prior), Pro-face BLUE(V3.3 Hotfix1 or prior).
CVE-2022-0222 1 Schneider-electric 28 Modicon M340 Bmxnoe0100, Modicon M340 Bmxnoe0100 Firmware, Modicon M340 Bmxnoe0110 and 25 more 2025-04-29 7.5 High
A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24)
CVE-2022-37301 1 Schneider-electric 96 Modicon M340 Bmx P34-2010, Modicon M340 Bmx P34-2010 Firmware, Modicon M340 Bmx P34-2030 and 93 more 2025-04-28 7.5 High
A CWE-191: Integer Underflow (Wrap or Wraparound) vulnerability exists that could cause a denial of service of the controller due to memory access violations when using the Modbus TCP protocol. Affected products: Modicon M340 CPU (part numbers BMXP34*)(V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*)(V3.22 and prior), Legacy Modicon Quantum/Premium(All Versions), Modicon Momentum MDI (171CBU*)(All Versions), Modicon MC80 (BMKC80)(V1.7 and prior)
CVE-2017-9631 1 Schneider-electric 1 Wonderware Archestra Logger 2025-04-20 7.5 High
A Null Pointer Dereference issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The null pointer dereference vulnerability could allow an attacker to crash the logger process, causing a denial of service for logging and log-viewing (applications that use the Wonderware ArchestrA Logger continue to run when the Wonderware ArchestrA Logger service is unavailable).
CVE-2017-9629 1 Schneider-electric 1 Wonderware Archestra Logger 2025-04-20 9.8 Critical
A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The stack-based buffer overflow vulnerability has been identified, which may allow a remote attacker to execute arbitrary code in the context of a highly privileged account.
CVE-2017-13997 1 Schneider-electric 2 Wonderware Indusoft Web Studio, Wonderware Intouch 2025-04-20 N/A
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.
CVE-2017-5178 1 Schneider-electric 3 Tableau Desktop, Tableau Server, Wonderware Intelligence 2025-04-20 N/A
An issue was discovered in Schneider Electric Tableau Server/Desktop Versions 7.0 to 10.1.3 in Wonderware Intelligence Versions 2014R3 and prior. These versions contain a system account that is installed by default. The default system account is difficult to configure with non-default credentials after installation, and changing the default credentials in the embedded Tableau Server is not documented. If Tableau Server is used with Windows integrated security (Active Directory), the software is not vulnerable. However, when Tableau Server is used with local authentication mode, the software is vulnerable. The default system account could be used to gain unauthorized access.
CVE-2017-14024 1 Schneider-electric 2 Wonderware Indusoft Web Studio, Wonderware Intouch 2025-04-20 N/A
A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges.
CVE-2016-8374 1 Schneider-electric 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more 2025-04-20 7.5 High
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker may be able to disrupt a targeted web server, resulting in a denial of service because of UNCONTROLLED RESOURCE CONSUMPTION.
CVE-2017-9961 1 Schneider-electric 1 Pro-face Gp Pro Ex 2025-04-20 N/A
A vulnerability exists in Schneider Electric's Pro-Face GP Pro EX version 4.07.000 that allows an attacker to execute arbitrary code. Malicious code installation requires an access to the computer. By placing a specific DLL/OCX file, an attacker is able to force the process to load arbitrary DLL and execute arbitrary code in the context of the process.
CVE-2017-6032 1 Schneider-electric 2 Modbus, Modbus Firmware 2025-04-20 N/A
A Violation of Secure Design Principles issue was discovered in Schneider Electric Modicon Modbus Protocol. The Modicon Modbus protocol has a session-related weakness making it susceptible to brute-force attacks.
CVE-2017-6030 1 Schneider-electric 6 Modicon M221, Modicon M221 Firmware, Modicon M241 and 3 more 2025-04-20 6.5 Medium
A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.
CVE-2017-6026 1 Schneider-electric 4 Modicon M241, Modicon M241 Firmware, Modicon M251 and 1 more 2025-04-20 9.1 Critical
A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised.
CVE-2017-6017 1 Schneider-electric 30 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 27 more 2025-04-20 N/A
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.
CVE-2017-6033 1 Schneider-electric 1 Interactive Graphical Scada System 2025-04-20 N/A
A DLL Hijacking issue was discovered in Schneider Electric Interactive Graphical SCADA System (IGSS) Software, Version 12 and previous versions. The software will execute a malicious file if it is named the same as a legitimate file and placed in a location that is earlier in the search path.
CVE-2017-6034 1 Schneider-electric 2 Modbus, Modbus Firmware 2025-04-20 N/A
An Authentication Bypass by Capture-Replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and download.
CVE-2017-9627 1 Schneider-electric 1 Wonderware Archestra Logger 2025-04-20 8.6 High
An Uncontrolled Resource Consumption issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The uncontrolled resource consumption vulnerability could allow an attacker to exhaust the memory resources of the machine, causing a denial of service.
CVE-2016-8352 1 Schneider-electric 6 Connexium Firmware, Tcsefec23f3f20, Tcsefec23f3f21 and 3 more 2025-04-20 N/A
An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code.
CVE-2017-7974 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files.
CVE-2016-8354 1 Schneider-electric 1 Unity Pro 2025-04-20 N/A
An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions.